It's difficult to PLC programming? Instance to explain how the PLC programming simplification -

by:Coolmay     2020-07-08
According to the chart of the three-phase ac motor and reversing control of main circuit, design a control system of PLC controller control motor is stopped. Control requirements are as follows:

1) Under normal circumstances, press the start button SB1, motor forward, reverse start button SB2, motor reversal.

( 2) After motor start, press the stop button SB3 and wait for 5 seconds later, can change the direction of rotation of the motor;

( 3) If the SB1 and SB2 press at the same time, the motor stop running, and don't start, at the same time alarm light L1 on 1 second dark flashing 1 SEC. Press SB3 stop button to reset at this time.

first we confirm button, use the auxiliary contact situation of KM, there is a positive &negative main circuit, main circuit must have an interlock circuit, the other button with normally open contacts.

it's PLC controller input and output point table:

according to the question ( 1) Programming: according to the question 1 here, and just over two since the hold circuit can be.

the question 2 for 5 seconds press the stop button to change the direction of motor, so there should be a flag bit in the set, here use M0. 0.

and interlock circuit and program, specific as follows:

in the first two since added to keep the loop interlock circuit - — Networks 1 Q0. 1 normally closed point, Q0 and network 2. 0 normally closed. Question 2 say 5 seconds after press the stop button, can press the start button, so the network 3 press I0. 2 after the stop button, M0. 0 to keep, timer T37 timing after 5 s, M0. 0 loop since hold off. And M0 are added into the network 1 and 2. 0 normally closed point, M0. 0 to electric network 1 and 2 even when pressing the forward button or reverse button didn't make Q0. 0 or Q0. 1 have to electricity.

the question 3 for SB1 and SB2 press at the same time, the motor stop running, and don't start, at the same time, the alarm light L1 on 1 second dark flashing 1 SEC. Programming is as follows:

this 4/5/6 increased network, network 5 and 6 is to use two timer to produce a small program for a second pulse, SM0. 0 for special, its function is always have electricity. Networks are 4 using M0. 1 will network 1/2/3 lock, that is to say, M0. 1 have to electric network. 2. 3 is not effective. A summary on its principle and M0. 0.

above all the programming is the instance. Is the so-called great oaks grow from little acorns, if you call small make up a breath made up, small make up also is very difficult. However, the question a little break up, a little to write the function of the required, finally certainly can satisfy your heart. Finally you see make up the program and the initial difference how much


programmable control systems are required in the manufacture of almost every product and plc controller price plc manufacturers is one of the most common machines.
As a global plc manufacturers company, we take on some of the world’s biggest plc manufacturers challenges. Shenzhen Coolmay Technology Co., Ltd. have a whole series of programmable control systems plc manufacturers that can solve your plc manufacturers problem in an effective manner. Check it at Coolmay PLC.
The same determination is critical for business owners. The journey in plc manufacturers business is both a challenging and rewarding experience.
plc manufacturers is attracting a great positive feedback from the customers. And many of our clients are fully satisfied with it.
Chat Online
Chat Online
Chat Online inputting...
Sign in with: